Autonomous Rack Cooling Layout Using Residual Airflow Reuse

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

Existing cooling systems for autonomous racks, particularly those lacking liquid cooling infrastructure, struggle to optimize the cooling of both liquid-cooled and air-cooled electronic components effectively, leading to potential component failure due to inadequate thermal management.

Innovation Solution

A dual-loop cooling system is implemented, comprising a front-mounted air-to-liquid heat exchanger for liquid-cooled components and a rear-mounted heat exchanger for air-cooled components, with separate liquid cooling loops and pumps to manage cooling fluid flow, optimizing temperature ranges for each component type.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Device complexity

If a single cooling system is used for both liquid-cooled and air-cooled components, then device complexity is reduced, but cooling efficiency and temperature optimization for each component type deteriorates

Engineering Contradiction:
Improvecooling system structureVSAvoidcooling efficiency
Core Design Contradiction:
Device complexityVSReliability

Solution Approach 1:

The cooling system is divided into two independent loops: a liquid cooling loop with liquid cooling units for liquid-cooled components, and an air cooling loop with air cooling units for air-cooled components. Each loop operates independently with its own heat exchangers, allowing optimized cooling for each component type without interference.

Inventive Principle:
Principle #1Segmentation

Solution Approach 2:

Different cooling methods are applied to different components based on their specific thermal requirements. Liquid cooling units serve liquid-cooled components while air cooling units serve air-cooled components, ensuring each component receives the appropriate cooling mode for optimal performance.

Inventive Principle:
Principle #3Local quality

2Temperature

If liquid cooling blocks are used to improve cooling performance, then temperature control improves, but device complexity and infrastructure requirements worsen

Engineering Contradiction:
Improvetemperature controlVSAvoidcooling infrastructure
Core Design Contradiction:
TemperatureVSDevice complexity

Solution Approach 1:

The system merges liquid cooling and air cooling approaches into a unified rack-level cooling system. The liquid cooling loop handles high-heat components while the air cooling loop manages other components, and both loops integrate into a single rack infrastructure with shared control and monitoring.

Inventive Principle:
Principle #5Merging (Combining)

Solution Approach 2:

The autonomous rack provides its own cooling infrastructure through integrated liquid cooling units and air cooling units, eliminating the need for external cooling infrastructure. The system independently manages thermal dissipation for all components within the rack.

Inventive Principle:
Principle #25Self-service

3Reliability

If forced ventilation fans are used to extract heated air, then air cooling improves, but energy consumption increases

Engineering Contradiction:
Improveair cooling performanceVSAvoidenergy consumption
Core Design Contradiction:
ReliabilityVSUse of energy by moving object

Solution Approach 1:

The system converts the waste heat from air-cooled components into a useful resource by directing it to the liquid cooling loop's heat exchanger. The heated air from air-cooled components passes through the liquid cooling heat exchanger, transferring heat to the cooling liquid and reducing the load on the liquid cooling system while simultaneously cooling the air.

Inventive Principle:
Principle #22Blessing in disguise (Convert harm into benefit)

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

This configuration enhances cooling efficiency by maintaining optimal temperature ranges for both types of components, reducing energy consumption, and allowing for higher server density in data centers by minimizing the need for additional cooling infrastructure.

Implementation Method 1

an air-to-liquid heat exchanger mounted on a front side of the rack structure and equipped with at least one fan. The heat exchanger is configured to pull in cold ambient air towards the first set of rack-mounted processing assemblies

Methodology Applied
Scientific EffectHeat exchange: Heat Exchanger

Implementation Method 2

at least one liquid cooling unit thermally mounted onto the at least one liquid-cooled heat-generating electronic component of the first set of processing assemblies and fluidly-coupled to the circulation conduit to internally channel the cooling liquid therethrough

Methodology Applied
Scientific EffectThermal conduction: Conduction (thermal)

Implementation Method 3

at least one first pump to forcibly urge the flow of the cooling liquid through the forward path, the liquid cooling unit, the return path, and the first air-to-liquid heat exchanger

Methodology Applied
Scientific EffectPumping: Pump

Implementation Method 4

mount fans on the backplanes of server racks that generate forced ventilation to extract heated air from the server racks and expel the heated air into the ambient environment

Methodology Applied
Scientific EffectForced convection: Forced Convection

Data Source

PatentEP4687385A1Cooling arrangements for autonomous racks
Publication Date: 2026.02.04 OVH
  • EP4687385A1 patent drawingFigure 1
  • EP4687385A1 patent drawingFigure 2
  • EP4687385A1 patent drawingFigure 3A~3B

AI summary

Autonomous rack system configurations for datacenter operations are presented that include a combination of a first rack structure incorporating front-mounted heat exchanger and a second rack structure incorporating a rear-mounted heat exchanger, such that liquid-cooled heat-generating electronic components that are less tolerant to higher temperatures are disposed within the first rack structure and liquid-cooled heat-generating electronic components that are more tolerant to higher temperatures are disposed within the second rack structure. These configurations utilize the residual air flow that passes through the less temperature tolerant electronic components of the first rack structure and redirect it to the second rack structure to cool the more temperature tolerant electronic components of the second rack structure.