Coolant Distribution Unit Layout for Live Liquid-Cooling Maintenance

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

Traditional air cooling methods are inadequate for effectively managing heat in high-power density electronic components, leading to overheating issues in data centers, which can degrade computing performance and reduce system lifetime.

Innovation Solution

A high-density liquid cooling system with a coolant distribution unit (CDU) that includes a rack-mounted liquid-to-liquid heat exchanger, bypass valves, and redundant pumping systems to maintain cooling capacity during maintenance, allowing for modular installation and serviceability without downtime.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Power

If traditional air cooling methods are used, then the system structure is simple, but heat removal capability is insufficient for high-power density electronic components

Engineering Contradiction:
Improveheat removal capabilityVSAvoidcooling system complexity
Core Design Contradiction:
PowerVSDevice complexity

Solution Approach 1:

The patent transitions from air cooling to liquid cooling by implementing a closed-loop hydraulic system with coolant circulation. The liquid cooling system uses pumps, heat exchangers, and distribution manifolds to efficiently remove heat from high-power density electronic components, achieving superior thermal management compared to traditional air cooling methods.

Inventive Principle:
Principle #29Pneumatics and hydraulics

2Power

If liquid cooling systems are implemented, then heat removal efficiency increases, but system complexity and installation difficulty increase

Engineering Contradiction:
Improveheat removal efficiencyVSAvoidinstallation ease
Core Design Contradiction:
PowerVSEase of manufacture

Solution Approach 1:

The cooling system is divided into modular components including separate distribution manifolds for primary and secondary loops, individual pump assemblies, and discrete heat exchanger units. This segmentation allows for easier installation, maintenance, and scalability, as components can be independently configured and replaced without affecting the entire system.

Inventive Principle:
Principle #1Segmentation

Solution Approach 2:

The distribution manifolds are designed with universal mounting interfaces and standardized connection points that can accommodate various electronic component configurations. The system can serve multiple functions including cooling different types of electronic components, supporting both primary and secondary coolant loops, and providing integrated flow distribution and collection in a single manifold structure.

Inventive Principle:
Principle #6Universality (Multi-functionality)

3Temperature

If coolant distribution units are added for liquid cooling, then thermal management improves, but pressure drops and power consumption increase

Engineering Contradiction:
Improvethermal managementVSAvoidpower consumption
Core Design Contradiction:
TemperatureVSUse of energy by moving object

Solution Approach 1:

The system employs variable speed pumps that can dynamically adjust their operating speed based on the thermal load and cooling requirements. This dynamic control allows the system to optimize power consumption by running pumps at lower speeds when full cooling capacity is not needed, while still maintaining effective thermal management when high heat removal is required.

Inventive Principle:
Principle #15Dynamics

Solution Approach 2:

The distribution manifolds incorporate flow distribution features that ensure adequate coolant flow to all required locations without excessive pressure losses. The system is designed to provide just sufficient cooling capacity for each zone rather than over-cooling, thereby reducing the overall power consumption of the pumping system while maintaining effective thermal management.

Inventive Principle:
Principle #16Partial or excessive action

4Power

If heat exchangers are installed for heat transfer, then cooling capacity increases, but system footprint and space requirements increase

Engineering Contradiction:
Improvecooling capacityVSAvoidsystem footprint
Core Design Contradiction:
PowerVSArea of stationary object

Solution Approach 1:

The heat exchanger is integrated within the distribution manifold structure, with the heat exchange surfaces nested within or attached to the manifold body. This nested configuration allows the heat exchanger to utilize the internal volume of the manifold, thereby reducing the overall system footprint while maintaining adequate cooling capacity. The compact integrated design eliminates the need for separate, space-consuming heat exchanger components.

Inventive Principle:
Principle #7Nested doll (Nesting)

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

The system efficiently transfers heat from secondary to primary coolant loops, reducing pressure drops and power consumption while enabling maintenance of components during operation, thereby extending the uptime and performance of data center equipment.

Implementation Method 1

CDUs typically include a liquid to liquid heat exchanger, which allows heat transfer from coolant in a secondary loop to a primary loop

Methodology Applied
Scientific EffectHeat transfer: Heat Exchanger

Data Source

PatentUS20250220851A1Coolant distribution unit and control system
Publication Date: 2025.07.03 HOFFMAN ENCLOSURES INC
  • US20250220851A1 patent drawing
  • US20250220851A1 patent drawing
  • US20250220851A1 patent drawing

AI summary

Embodiments of the invention provide a system and method for housing electrical components of a high-density liquid cooling unit to liquid cool electrical components. The system includes a first electrical cabinet housing at least one electrical switch and a controller. The first electrical cabinet is swingable outward to open, and the first electrical cabinet opens while the high density liquid cooling system continues to operate to liquid cool electrical components. The system includes a second electrical cabinet housing a first motor drive and a second motor drive. The second electrical cabinet is accessible when the first electrical cabinet swings outward. One of the first motor drive and the second motor drive are replaceable while the high density liquid cooling unit continues to operate.