D2C Coolant Flow Control Using Peak Server Power Signals

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

Conventional direct-to-chip (D2C) liquid cooling systems in data centers face delays in responding to rapid changes in IT loads due to thermal resistances and physical distances, leading to inefficient coolant flow adjustments and potential overheating of microchip assemblies.

Innovation Solution

A system that monitors real-time power draws of IT devices to identify the highest power consumption and adjusts coolant flow rate and supply temperature dynamically, bypassing delays associated with thermal resistances and physical distances to maintain microchip assemblies within their temperature thresholds.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Reliability

If coolant flow rate is adjusted based on peak IT load and maximum chip temperature, then microchip assemblies are maintained below maximum junction temperature, but flow rate exceeds what is needed during varying IT loads

Engineering Contradiction:
Improvemicrochip temperature controlVSAvoidcoolant flow rate
Core Design Contradiction:
ReliabilityVSUse of energy by moving object

Solution Approach 1:

The system dynamically adjusts coolant flow rate based on real-time power draw measurements from IT devices. The controller continuously monitors power consumption and modifies pump speed to match actual thermal loads, transitioning from static peak-load-based control to dynamic demand-based control, thereby reducing energy consumption while maintaining temperature reliability

Inventive Principle:
Principle #15Dynamics

Solution Approach 2:

The system implements feedback control by measuring power draw from IT devices and using this information to adjust coolant flow rate. The controller receives real-time power consumption data and continuously modifies cooling output to match actual thermal generation, creating a closed-loop system that optimizes energy efficiency while ensuring temperature control

Inventive Principle:
Principle #23Feedback

2Temperature

If coolant flow rate is increased to handle peak thermal loads, then microchip assemblies are cooled effectively, but energy expenditure increases unnecessarily during lower loads

Engineering Contradiction:
Improvemicrochip junction temperatureVSAvoidcooling system energy consumption
Core Design Contradiction:
TemperatureVSLoss of energy

Solution Approach 1:

The system changes the operating parameters of the cooling system by adjusting pump speed and coolant flow rate based on measured power draw. Instead of maintaining constant high flow rate, the system varies flow parameters dynamically to match actual thermal demands, reducing energy loss during low-load conditions while maintaining adequate cooling capacity when needed

Inventive Principle:
Principle #35Parameter changes

3Reliability

If thermal management responds to temperature changes, then overheating is prevented, but response delay occurs due to thermal resistances and physical distances

Engineering Contradiction:
Improveoverheating preventionVSAvoidthermal management response time
Core Design Contradiction:
ReliabilityVSLoss of time

Solution Approach 1:

The system performs preliminary action by measuring power draw from IT devices before significant temperature changes occur. Since power consumption directly correlates with heat generation, the controller can proactively adjust coolant flow rate in response to power draw changes rather than waiting for temperature sensors to detect overheating conditions, thereby reducing response delay

Inventive Principle:
Principle #10Preliminary action

Solution Approach 2:

The system uses power draw measurement as an intermediary parameter to predict thermal conditions. Instead of directly responding to temperature changes through thermal conduction, the system uses electrical power measurement (which provides immediate feedback) as a proxy for thermal load, enabling faster response time while maintaining reliable overheating prevention

Inventive Principle:
Principle #24Intermediary (Mediator)

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

Enables immediate response to IT load changes, preventing overheating while minimizing energy expenditure by adjusting coolant flow and temperature based on actual power demands, thus optimizing thermal management and reducing unnecessary energy consumption.

Implementation Method 1

Single-phase direct-to-chip (D2C) liquid cooling is a viable solution for heat collection and dissipation whereby dedicated coolant distribution units (CDU) deliver liquid coolant at a set flow rate and temperature to coldplates or heat exchangers proximate to the chip

Methodology Applied
Scientific EffectThermal conduction: Conduction (thermal)

Implementation Method 2

The CDU regulates the temperature of each microchip assembly, e.g., maintains the microchip assembly below its maximum junction temperature, by circulating liquid coolant through the microchip assemblies according to a predetermined coolant flow rate

Methodology Applied
Scientific EffectConvection: Convection

Data Source

PatentUS20260079505A1System and method for energy saving control of thermal management
Publication Date: 2026.03.19 VERTIV CORP
  • US20260079505A1 patent drawing
  • US20260079505A1 patent drawing
  • US20260079505A1 patent drawing

AI summary

A direct-to-chip (D2C) cooling system maintains microchip assemblies within their optimal junction temperature ranges by circulating liquid coolant into contact with the microchip assemblies for heat transfer therefrom. A coolant distribution unit (CDU) controller directly monitors (via a power distribution unit supplying operating power to the servers) power drawn by each of a set of servers, switches, or other information technology (IT) devices and/or microchip assemblies disposed therein, determining on a continual basis which IT device is currently drawing the most power and directing the CDU of the D2C system to dynamically adjust the flow rate setpoint for the liquid coolant supply based on the current highest power draw.