Dual-Loop Immersion Cooling with Cold Plates for HPC Chips

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

In high-performance computing environments, such as data centers, the existing immersion cooling systems face challenges in effectively cooling high-performance semiconductor chips due to high fluidic impedance in narrow spaces between circuit boards, leading to insufficient heat transfer from these chips to the cooling liquid.

Innovation Solution

The implementation of a dual primary cooling loop system, where a colder and faster fluid flow is directed through cold plates mounted on high-performance chip packages, overcoming the impedance issues and enhancing heat removal capabilities.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Device complexity

If a single primary cooling loop is used in immersion cooling systems, then the system structure is simple, but the heat transfer efficiency from high-performance semiconductor chips is insufficient due to high fluidic impedance in narrow spaces

Engineering Contradiction:
Improvecooling system structureVSAvoidchip temperature
Core Design Contradiction:
Device complexityVSTemperature

Solution Approach 1:

The cooling system is segmented into two independent primary loops: a first primary loop that circulates cooling fluid through the immersion chamber to cool general electronics, and a second primary loop that specifically targets high-performance semiconductor chips through cold plates. This segmentation allows each loop to be optimized for its specific cooling task, overcoming the fluidic impedance issues in narrow spaces by providing dedicated high-flow paths for high-heat-generation components.

Inventive Principle:
Principle #1Segmentation

2Volume of moving object

If cooling fluid flows through narrow spaces between circuit boards, then the system maintains compact arrangement, but fluidic impedance increases causing insufficient heat transfer

Engineering Contradiction:
Improvespace utilizationVSAvoidheat transfer efficiency
Core Design Contradiction:
Volume of moving objectVSProductivity

Solution Approach 1:

Cold plates are introduced as intermediary heat transfer devices mounted on high-performance chip packages. These cold plates provide dedicated fluid flow channels that bypass the narrow spaces between circuit boards, eliminating fluidic impedance issues while maintaining the compact immersion chamber arrangement. The cold plates act as mediators between the chips and the cooling fluid, ensuring efficient heat transfer without requiring increased spacing.

Inventive Principle:
Principle #24Intermediary (Mediator)

3Ease of operation

If a single cooling loop is used, then the system is easy to operate, but it cannot provide both general immersion cooling and targeted cold plate cooling simultaneously

Engineering Contradiction:
Improvesystem operationVSAvoidcooling mode flexibility
Core Design Contradiction:
Ease of operationVSAdaptability or versatility

Solution Approach 1:

The cooling system is divided into two independent primary loops with separate pumps, heat exchangers, and fluid pathways. The first primary loop handles general immersion cooling of the chamber, while the second primary loop specifically serves cold plates mounted on high-performance chips. This segmentation enables simultaneous operation of both cooling modes without interference, while each loop can be independently controlled and optimized for its specific function.

Inventive Principle:
Principle #1Segmentation

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

This approach allows for more efficient cooling of high-performance semiconductor chips by ensuring a colder and faster fluid flow, thereby improving heat transfer and reducing the temperature of the chips, even in constrained spaces.

Implementation Method 1

The liquid 102 has a higher heat transfer coefficient than air which enables heat to be removed from the electrical components more effectively

Methodology Applied
Scientific EffectConvection: Convection

Implementation Method 2

The heat exchanger 106 transfers heat from the warmed fluid to another liquid within a secondary cooling loop 107

Methodology Applied
Scientific EffectHeat exchange: Heat Exchanger

Data Source

PatentUS20240064931A1Immersion cooling system with first and second primary loops
Publication Date: 2024.02.22 INTEL CORP
  • US20240064931A1 patent drawing
  • US20240064931A1 patent drawing
  • US20240064931A1 patent drawing

AI summary

An apparatus is described. The apparatus includes a coolant distribution unit having a first primary loop output to provide first cooled immersion liquid to an immersion chamber and a second primary loop output to provide second cooled immersion liquid to one or more cold plates within the immersion chamber.