Pluggable Datacenter Cooling Loop With Intermediary Heat Exchange

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

Existing datacenter cooling systems, particularly air cooling, are inefficient for high-density servers, and liquid cooling systems pose risks of electrical shorting and flooding, lacking universality and complicating design, serviceability, and reliability.

Innovation Solution

A universal integrated pluggable mezzanine module with a flexible tubing system and snap-in connections for a universal coolant, integrating an additional cooling loop with a heat exchanger to transfer heat to a primary cooling loop via a cooling distribution unit, eliminating the need for system-specific wetted materials.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Loss of energy

If liquid cooling systems are used to draw heat away from server components, then cooling efficiency is improved, but the risk of electrical shorting and flooding increases

Engineering Contradiction:
Improvecooling efficiencyVSAvoidrisk of electrical shorting and flooding
Core Design Contradiction:
Loss of energyVSReliability

Solution Approach 1:

The patent introduces an intermediary cooling loop with dielectric fluid that transfers heat from the server components indirectly. The first cooling loop uses dielectric fluid to cool components, the second loop uses water to cool the first loop via heat exchangers, and the third loop uses chilled water from a CDU to cool the second loop. This multi-layered intermediary system maintains high cooling efficiency while eliminating direct water contact with electrical components, thus preventing electrical shorting and flooding risks.

Inventive Principle:
Principle #24Intermediary (Mediator)

2Loss of energy

If system-specific wetted materials are used for different cooling systems, then cooling performance is optimized, but device complexity and manufacturing difficulty increase

Engineering Contradiction:
Improvecooling performanceVSAvoidsystem-specific wetted materials
Core Design Contradiction:
Loss of energyVSDevice complexity

Solution Approach 1:

The patent implements a universal cooling system where the same dielectric fluid is used across all server trays and rack units regardless of specific cooling requirements. The system can accommodate different server densities and cooling needs through adjustable flow rates and heat exchanger configurations rather than requiring different wetted materials. This universal approach simplifies manufacturing, reduces part variety, and eliminates the complexity of matching specific materials to specific cooling applications while maintaining optimized cooling performance through system adjustments.

Inventive Principle:
Principle #6Universality (Multi-functionality)

3Loss of energy

If visible tubing systems are installed for liquid cooling, then heat transfer capability is improved, but the risk of leaks and damage increases

Engineering Contradiction:
Improveheat transfer capabilityVSAvoidrisk of leaks and damage
Core Design Contradiction:
Loss of energyVSObject-affected harmful factors

Solution Approach 1:

The patent embeds the cooling tubing and heat exchangers within the rack structure itself rather than using external visible tubing. The first cooling loop tubing is routed through integrated channels in the rack units, and heat exchangers are mounted within the rack enclosure. This nesting approach maintains effective heat transfer capability while protecting the tubing from external damage and reducing leak risks by eliminating exposed connections and external routing.

Inventive Principle:
Principle #7Nested doll (Nesting)

4Power

If cooling systems are designed for high-density servers, then cooling capacity is improved, but adaptability to different server configurations decreases

Engineering Contradiction:
Improvecooling capacityVSAvoidadaptability to different server configurations
Core Design Contradiction:
PowerVSAdaptability or versatility

Solution Approach 1:

The patent employs a dynamic cooling system where the flow rate of dielectric fluid through the first cooling loop can be adjusted based on the specific thermal load and configuration of servers in each rack unit. The system can adapt to different server densities, power consumptions, and thermal characteristics by varying pump speeds and flow distribution without requiring redesign for each configuration. This dynamic adjustability maintains high cooling capacity for dense configurations while providing versatility across different server arrangements.

Inventive Principle:
Principle #15Dynamics

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

Enables efficient and reliable cooling of high-density servers without visible tubing, allowing for component changes without downtime, and reducing the risk of leaks and damage, while maintaining consistent cooling performance.

Implementation Method 1

a first cooling loop with a heat exchanger to exchange heat with a second cooling loop

Methodology Applied
Scientific EffectHeat exchanger: Heat Exchanger

Implementation Method 2

the second cooling loop includes a cooling distribution unit (CDU) to exchange heat between the second cooling loop and a primary cooling loop

Methodology Applied
Scientific EffectHeat exchange: Heat Exchanger

Data Source

PatentUS20250374478A1Universal pluggable datacenter cooling system
Publication Date: 2025.12.04 NVIDIA CORP
  • US20250374478A1 patent drawing
  • US20250374478A1 patent drawing
  • US20250374478A1 patent drawing

AI summary

A datacenter cooling system is disclosed. The system includes a first cooling loop with a heat exchanger to exchange heat with a second cooling loop. The second cooling loop includes a cooling distribution unit (CDU) to exchange heat between the second cooling loop and a primary cooling loop.