Transformer Fault Detection via TTR Monitoring

Resolve Bottlenecks,
Find Innovative Solutions
Generate Solutions

Solution Overview

Problem

Existing methods for monitoring distribution transformers are inadequate for timely identification of faults, particularly due to safety concerns and practical limitations when measuring transformer turns ratio (TTR) in service, which can lead to cascading short circuits and potential overheating or property damage.

Innovation Solution

A transformer fault detection system that measures primary and secondary voltages simultaneously, calculates the transformer turns ratio (TTR), and uses wireless communication to compare changes in TTR values, allowing for proactive intervention before a complete breakdown, incorporating a switching device with voltage measurement, data logging, and wireless communication systems.

Engineering Contradictions & Design Principles

VSEngineering Contradiction Analysis

1Reliability

If visual inspection methods (infrared camera, pop-up valve monitoring) are used to monitor transformer degradation, then safety risks are reduced, but fault detection timing is insufficient leading to cascading short circuits

Engineering Contradiction:
Improvefault detection timingVSAvoidresponse time to fault
Core Design Contradiction:
ReliabilityVSProductivity

Solution Approach 1:

The system performs preliminary action by continuously monitoring transformer parameters (temperature, voltage, current, TTR) and detecting early signs of winding shorts before they develop into complete failures. The TTR monitoring specifically detects turns loss in advance, allowing preventive maintenance before cascading short circuits occur.

Inventive Principle:
Principle #10Preliminary action

Solution Approach 2:

The system implements feedback through continuous real-time monitoring of transformer parameters and automatic alert generation when fault conditions are detected. The system provides feedback loops that track TTR changes, temperature variations, and electrical parameter deviations to enable timely intervention.

Inventive Principle:
Principle #23Feedback

2Measurement precision

If TTR measurement is performed using traditional open-circuit method during manufacturing, then measurement precision is achieved, but the method cannot be applied to in-service transformers due to safety and practical limitations

Engineering Contradiction:
ImproveTTR measurement capabilityVSAvoidapplicability to in-service transformers
Core Design Contradiction:
Measurement precisionVSEase of operation

Solution Approach 1:

The system uses an intermediary approach by measuring TTR through voltage and current sensors that can be connected to live transformers without requiring open-circuit conditions. The monitoring device acts as an intermediary that safely interfaces with in-service transformers to extract TTR information without disrupting normal operation or requiring high voltage test equipment.

Inventive Principle:
Principle #24Intermediary (Mediator)

Solution Approach 2:

The system changes the measurement parameters from traditional open-circuit voltage ratio measurement to continuous monitoring of voltage, current, and impedance parameters under load conditions. This allows TTR to be calculated indirectly through electrical parameter relationships that remain valid during normal transformer operation.

Inventive Principle:
Principle #35Parameter changes

3Productivity

If transformers are operated without maintenance for extended periods, then operational efficiency is maintained, but undetected winding shorts lead to overheating and property damage

Engineering Contradiction:
Improvecontinuous operation durationVSAvoidoverheating and property damage risk
Core Design Contradiction:
ProductivityVSObject-affected harmful factors

Solution Approach 1:

The system enables self-service monitoring where the transformer's own operational parameters (voltage, current, temperature, TTR) are continuously measured and analyzed to detect its own degradation. This allows the transformer to essentially monitor itself for signs of winding shorts without requiring external manual inspection.

Inventive Principle:
Principle #25Self-service

Solution Approach 2:

The system replaces manual mechanical inspection methods with automated electronic monitoring. Instead of physical visual inspections using infrared cameras or pressure gauges, the system uses electronic sensors and digital processing to continuously monitor electrical parameters and detect faults automatically.

Inventive Principle:
Principle #28Mechanics substitution (Replace mechanical system)

Applied Scientific Principles

This section explains which scientific principles are used to turn an abstract innovation direction into a practical engineering solution.

Function Achieved in This Case

Enables early detection of transformer faults, allowing for safe removal from service or dispatch of maintenance crews, reducing the risk of extended power outages and property damage by identifying changes in TTR values indicative of winding shorts.

Implementation Method 1

an electrical distribution transformer strategically positioned along the lateral lines, and the low voltage is then provided to a number of loads... a primary winding coupled to a medium voltage power line and a secondary winding providing a stepped down voltage of the medium voltage

Methodology Applied
Scientific EffectElectromagnetic induction: Electromagnetic Induction

Data Source

PatentUS11585865B2Transformer fault detection system
Publication Date: 2023.02.21 S&C ELECTRIC CO
  • US11585865B2 patent drawing
  • US11585865B2 patent drawing

AI summary

A transformer fault detection, where the transformer includes a primary winding coupled to a medium voltage power line and a secondary winding providing a stepped down voltage of the medium voltage. The detection system includes a switching device, where the switching device includes a first voltage measuring device for measuring the voltage on the primary winding, a controller for processing measured voltages and a transceiver for receiving and transmitting messages. The detection system also includes a second voltage measuring device for measuring the stepped down voltage on the secondary winding, where the second voltage measuring device includes a transmitter for transmitting the measured step down voltage to the switching device. The controller uses the measured voltages to calculate a transformer turns ratio (TTR) of the transformer to determine whether a transformer fault.