A High Voltage Ride-Through Control Method for Two-Stage Photovoltaic Grid-Connected Systems
By adjusting the reactive current reference value in the two-stage photovoltaic grid-connected system, the problem of active power loss during high-voltage faults was solved, reactive power absorption and DC bus voltage stabilization were achieved, and the high-voltage ride-through capability of the system was improved.
Patent Information
- Authority / Receiving Office
- CN · China
- Patent Type
- Patents(China)
- Current Assignee / Owner
- PANZHIHUA POWER SUPPLY COMPANY STATE GRID SICHUAN ELECTRIC POWER
- Filing Date
- 2022-07-15
- Publication Date
- 2026-05-26
AI Technical Summary
Existing high-voltage ride-through control strategies in photovoltaic grid-connected systems are costly and difficult to control, and result in severe active power loss during high-voltage faults, leading to high grid disconnection frequency.
A high-voltage ride-through control method for a two-stage photovoltaic grid-connected system is adopted. By controlling the downstream grid-connected inverter to continuously output the same active power as when there is no fault, and adjusting the reactive current reference value according to the voltage change at the grid connection point, reactive power is absorbed to stabilize the DC bus voltage and reduce the voltage at the grid connection point.
Without adding hardware circuitry, the high-voltage ride-through capability of the photovoltaic grid-connected system is improved, active power is kept stable, grid connection point voltage fluctuations are reduced, and the system's fault ride-through capability is enhanced.
Smart Images

Figure CN115051411B_ABST