The method of local fire extinguishing by controlling the droplet size of hexafluoropropane to reach 8b level
A technology of hexafluoropropane and droplet size, which is applied in fire rescue and other fields, and achieves the effects of broad application prospects, high success rate of fire extinguishing, and wide application range
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment Construction
[0025]In May 2012, under normal outdoor conditions, according to different nozzle numbers, nozzle numbers, installation heights (height from oil surface to nozzles), and filling pressure, 8B level fire extinguishing tests were carried out 15 times, and the test conditions all met GB4351.1-2005 And the standard of Class B fire test and local application fire extinguishing test in GA602-2006, that is, the wind speed is not greater than 3m / s, there is no bad weather such as rain, snow or hail, the ambient temperature is -40°C-55°C, and the relative humidity is 45%-75%, atmospheric pressure 86KPa-106KPa. Use a suspended hexafluoropropane fire extinguishing device (Hangzhou Fire Fighting Equipment Co., Ltd., model XQLW1 / 0.5), the amount of hexafluoropropane is 0.5kg, and a standard atomizing nozzle is used. The nozzle is circular, with a diameter of 21mm, and the nozzle is equilateral There are 3 rotating cores evenly distributed in a triangle shape, the distance from the center of...
PUM
Login to View More Abstract
Description
Claims
Application Information
Login to View More 