Method for optimizing generator set cold end system with counter-flow mechanical draft cooling tower
A ventilation cooling and system optimization technology, applied to steam/steam condensers, heat exchange equipment, lighting and heating equipment, etc., to achieve the effect of low coal consumption rate for power supply
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment
[0116] Taking a 200MW gas-steam combined cycle generator set in a power plant as an example, the dry bulb temperature of the atmosphere is 31.1°C, the wet bulb temperature is 27.1°C, and the atmospheric pressure is 99.3kPa. The cold end system of the unit consists of 1 condenser, 4 The circulating water pump of the same type and 6 cooling tower fans of the same type are composed. The circulating water pump operates at power frequency, and the fans have no low-speed operation mode. The condenser data are shown in Table 1.
[0117] Table 1 Condenser data
[0118]
[0119] In addition, the correction coefficient in the HEI overall heat transfer coefficient calculation formula can be obtained by looking up the table or looking up the map.
[0120] According to the equipment type of circulating water pump and fan, there are 24 combinations in total. The conventional operation mode is 4 circulating water pumps and 6 fans, 3 circulating water pumps and 5 fans, 2 circulating water p...
PUM
Login to View More Abstract
Description
Claims
Application Information
Login to View More 


