Evaluation method on transformer oil
A transformer oil and evaluation method technology, applied in the direction of material inspection products, etc., can solve problems such as methods that cannot provide transformer oil and transformer oil anti-oxidation performance, and achieve good technical effects
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0018] Set a bare and loaded transformer in the transformer oil A1, so that the transformer oil is in full contact with the transformer; among them, the test conditions of the transformer oil are: temperature 85 ℃, oxygen flow rate 25 ml / min, voltage 6000 volts; the test conditions of the transformer For: primary voltage 300 volts, secondary voltage 200 volts, load current 2.5 amps.
[0019] Test the acid value of the test transformer oil. When the acid value is 0.1 mg KOH / g, record the test time as 2720 hours, and use this time to evaluate the oxidation resistance of the test transformer oil.
Embodiment 2
[0021] Same as [Example 1], evaluate the antioxidant performance of A1 oil sample. Only the test conditions for transformer oil are: temperature 98°C, oxygen flow rate 40 ml / min, voltage 9000 volts; test conditions for transformers are: primary voltage 380 volts, secondary voltage 250 volts, load current 5 amps.
[0022] Test the acid value of the test transformer oil. When the acid value is 0.1 mg KOH / g, record the test time as 1560 hours, and use this time to evaluate the oxidation resistance of the test transformer oil.
Embodiment 3~8
[0024] Same as [Example 1], evaluate the antioxidant properties of A1, A2, A3, B, D and C oil samples. Only the test conditions for transformer oil are: temperature 95°C, oxygen flow rate 40 ml / min, voltage 8100 volts; test conditions for transformers are: primary voltage 330 volts, secondary voltage 220 volts, load current 4.5 amps.
[0025] Test the acid value of the test transformer oil, when the acid value is 0.1 mg KOH / g, record the test time. See Table 2 for details.
[0026] Table 2
[0027] oil sample
[0028] It can be seen from Table 2 that according to the test time, the order of evaluating the performance of the test oil samples is: A3, A2, D, A1, B, C. The test evaluation results are completely consistent with the performance analysis and actual application of the test samples. That is: A2, A3 oil samples are Class I, transformer oils with good performance; A1, B, D oil samples are Class II transformer oils with good performance, and C oil samples are...
PUM
Login to View More Abstract
Description
Claims