Vortex street flow mixer for dry-wet type cooling tower fog dispersal
A technology of cooling towers and mixers, applied in the direction of water shower coolers, direct contact heat exchangers, heat exchanger types, etc., can solve the problem of low mixing efficiency of mixers, and achieve the effect of avoiding local fogging
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment approach 1
[0019] Implementation mode one: if image 3 As shown, the vortex street mixer is set at the lower part of the dry area, and the strip-shaped obstacles are arranged in two rows on the left and right. The two rows of strip-shaped obstacles are symmetrical about the vertical central axis of the cooling tower, and the lower end of the strip-shaped obstacles is located in the dry area. The bottom of the air inlet of the heat exchanger is close to the side wall of the dry zone, and the upper end is lower than the air inlet section of the fan and close to the vertical central axis plane of the cooling tower. The acute angle between the strip obstacle and the horizontal plane is greater than 30 degrees.
[0020] The width L of the strip obstacle is set within the range of [0.5m, 1m]. The distance S between adjacent bar-shaped obstacles is set to be 0.8 to 1.2 times longer than L. The section of the bar-shaped obstacle selected in this embodiment is an isosceles triangle, which is sh...
Embodiment approach 2
[0022] Implementation mode two: if Figure 4 As shown, the vortex street mixer is set at the upper position of the dry area, and the strip-shaped obstacles are arranged in two rows on the left and right. The two rows of strip-shaped obstacles are symmetrical about the vertical central axis of the cooling tower. The position of the air inlet section, the lower end is located close to the vertical central axis plane of the cooling tower, and the upper end of the bar-shaped obstacle is closer to the side wall of the dry zone than the lower end. The acute angle between the bar-shaped obstacle and the horizontal plane is greater than 30 degrees, and the angle between the bar-shaped obstacle and the vertical central axis plane of the cooling tower is controlled between 30 and 60 degrees.
[0023] The width L of the strip obstacle is set within the range of [0.5m, 1m]. The distance S between adjacent bar-shaped obstacles is set to be 0.8 to 1.2 times longer than L. The section of t...
PUM
Login to View More Abstract
Description
Claims
Application Information
Login to View More 


