Identification method of single-phase ground fault and phantom ground fault based on full-cycle energy ratio
A single-phase ground fault and phantom grounding technology, which is applied in the direction of measuring electricity, measuring devices, and measuring electrical variables, can solve the problems of unfavorable detection of single-phase ground faults, long time windows, etc., and achieve good timeliness and hardware sampling rate. The effect of low requirements and simple principle
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0039] Embodiment 1: as figure 1 Shown: 110kV / 35kV distribution network single-phase ground fault simulation model, the power supply voltage in the figure is 110kV, which is changed to 35kV by the transformer and then sent to the load end. It has 6 feeders, and the neutral point of the Z-shaped transformer passes through the arc suppression Coil series resistor to ground. overhead feeder L 1 =15km, L 3 =18km, L 5 =30km, wire-cable hybrid feeder L 4 =17km, the overhead feeder is 12km, the cable is 5km, and the cable feeder L 2 =6km, L 6=8km. Among them, the overhead feeder is JS1 rod type, LGJ-70 type conductor, the span is 80m, and the cable feeder is YJV23-35 / 95 type cable. G in the power grid is an infinite power source; T is the main transformer, the transformation ratio is 110kV / 35kV, and the connection group is Y N / d11;T Z Is a zigzag transformer; L is the arc suppression coil; R is the damping resistance of the arc suppression coil. The feeder adopts th...
Embodiment 2
[0042] Embodiment 2: The single-phase ground fault simulation model of the 110kV / 35kV distribution network is the same as that of Embodiment 1, and the distance from the feeder L 1 A single-phase ground fault occurs at 5km from the beginning, the ground resistance is 20Ω, the fault angle is 90°, and the sampling frequency is 10kHz.
[0043] According to the same method as in Example 1, the feeder L 1 The zero-sequence voltage waveform is as image 3 Shown, and obtain the highest frequency energy value ratio of the first cycle and the second cycle =13198> ρ set =1.5, so it can be judged that the feeder L 1 It is a single-phase ground fault feeder.
Embodiment 3
[0044] Embodiment 3: The simulation model of the 110kV / 35kV distribution network system is the same as in Embodiment 1. After the voltage value exceeds the limit, two cycles of zero-sequence voltage data are obtained.
[0045] The steps of the single-phase ground fault and phantom ground fault identification method based on the full-cycle energy ratio are the same as those in Embodiment 1.
[0046] The zero-sequence voltage waveform obtained by the simulation experiment is as follows: Figure 4 Shown, and obtain the highest frequency energy value ratio of the first cycle and the second cycle =1.2943 =1.5, so it can be judged that the phantom grounding phenomenon has occurred in the system.
[0047] In addition, the highest frequency energy ratio of the first cycle and the second cycle after the fault under different fault angles and phantom grounding conditions is shown in Table 1. The ratio is much greater than 1 in the case of a single-phase ground fault, and close to 1 i...
PUM
Login to View More Abstract
Description
Claims
Application Information
Login to View More 