Method for checking and testing relay protection vector before operation of newly-built transformer station
A relay protection and substation technology, applied in the field of relay protection vector inspection and testing, can solve the problems of metering errors, affecting the normal operation of power equipment, and time-consuming, and achieve the effect of preventing misoperation or refusal to operate
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0036] Embodiment 1 is the specific steps of the inspection test method when adopting transmission line crossing short circuit:
[0037] (1) Adjust the operating status of the tested primary and secondary equipment:
[0038] a. When the double-bus connection is in the form, the branch circuit under test (referring to the transmission line, the transmission line connected to the busbar, the branch circuit connected to the transformer under test) and the test equipment access branch circuit (transformer under test with the same voltage level) or another transmission line) running on different busbars (with figure 1 As shown in the example, if the tested branch runs on the bus V1, the CB2-1 switch and CB2 circuit breaker of the branch are in the running state, and the test equipment connected to the branch will run on the bus V2, that is, CB1-2 Knife switch and CB1 circuit breaker are in running state; on the contrary, if the tested branch runs bus V2, the test equipment connect...
Embodiment 2
[0054] Embodiment 2 is the specific steps of the inspection test method when adopting the tested transformer to ride through the short circuit:
[0055] (1) Adjust the operating status of the transformer under test and its secondary equipment:
[0056] The current transformer on one side of the transformer under test is short-circuited on the busbar side, and the grounding switch on the circuit breaker side can be used to complete this task (see figure 2 As shown, take the 220kV side short circuit as an example, make CB1-ES in the close position, make the CB1 circuit breaker in the close position, and CB1-1, CB1-2 switch in the open state); the tested relay protects each secondary equipment In the normal operation state, the current and voltage secondary circuits are in normal operation state, and the secondary equipment that needs to be set has been set.
[0057] (2) Connect the tested transformer to the bus side of the current transformer on the other voltage level side of...
Embodiment 3
[0071] Embodiment 3: The test of embodiment 3 has been extended to the local substation, mainly testing the current differential protection vector of the transmission line and the bus current differential protection vector of the transmission line in the opposite substation. During the test, the bus side of the current transformer at the opposite end of the line is short-circuited, and the test current is added from the substation on this side to mainly check the line current differential protection; change the position of the short-circuit point to the bus-tie circuit breaker (need to vacate a bus for testing) current transformer At the opposite end substation, the transmission line of the opposite end substation can be connected to the vector of bus differential protection; when a bus is vacated for testing, it can be changed from the short circuit method to the access test reactor method, and the opposite end station of the transmission line can be Vector check of line imped...
PUM

Abstract
Description
Claims
Application Information

- R&D
- Intellectual Property
- Life Sciences
- Materials
- Tech Scout
- Unparalleled Data Quality
- Higher Quality Content
- 60% Fewer Hallucinations
Browse by: Latest US Patents, China's latest patents, Technical Efficacy Thesaurus, Application Domain, Technology Topic, Popular Technical Reports.
© 2025 PatSnap. All rights reserved.Legal|Privacy policy|Modern Slavery Act Transparency Statement|Sitemap|About US| Contact US: help@patsnap.com