Method and system for recognizing lightning strike failure and lightning strike failure type of power transmission line
A technology for lightning strike faults and power transmission lines, which can be applied to fault locations, information technology support systems, and power measurement, and can solve problems such as poor reliability
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0101] The 500kV double-circuit line A and B on the same tower has a total length of 186.642 kilometers. A set of fault detection devices is installed on the No. 267 tower at the 125.37km point at the head end of the line.
[0102] One day the fault tripped, and the fault detection device installed on the No. 267 tower detected the fault traveling wave current, and its signal was as follows: Figure 4 As shown, wave header information is shown in Table 2.
[0103] Table 2 Fault traveling wave header information
[0104]
[0105] It can be seen from Table 2 that the polarity of phase B is opposite to AC, and the line can be preliminarily determined to be a shielding or non-lightning fault. The current change rate R of phase B of the fault phase is 7.175, which is less than 50, so it is judged as a single-phase ground fault.
[0106] After the inspection, it was found that the right ground wire of N35-N36 of the above-mentioned 500kV A line was broken, and one end of the bro...
Embodiment 2
[0108] The total length of the 500kV line is 148.440km. A phase fault tripped on a certain day. The fault detection device detects the fault traveling wave current, and its signal is as follows: Figure 5 As shown, wave header information is shown in Table 3.
[0109] Table 3 Fault traveling wave header information
[0110]
[0111] It can be seen from Table 3 that the polarity of phase A is opposite to that of BC, and the line can be preliminarily determined to be a shielding or non-lightning fault. The current change rate R of phase A of the fault phase is 77, which is greater than 50, so it is judged as a shielding fault.
[0112] After the inspection, it was found that there were traces of flashover discharge on the A-phase conductor and voltage equalizing shielding ring of a tower of the above-mentioned 500kV line. The inspection facts are consistent with the judgment conclusion of this embodiment.
PUM
Abstract
Description
Claims
Application Information
- R&D Engineer
- R&D Manager
- IP Professional
- Industry Leading Data Capabilities
- Powerful AI technology
- Patent DNA Extraction
Browse by: Latest US Patents, China's latest patents, Technical Efficacy Thesaurus, Application Domain, Technology Topic, Popular Technical Reports.
© 2024 PatSnap. All rights reserved.Legal|Privacy policy|Modern Slavery Act Transparency Statement|Sitemap|About US| Contact US: help@patsnap.com