A load distribution optimization configuration method for central air-conditioning refrigeration system
A technology for optimizing configuration and system load, applied in mechanical equipment and other directions, can solve problems such as restricting the development of central air conditioning systems, and achieve the effect of improving work efficiency and optimizing energy consumption
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Image
Examples
Embodiment 1
[0123] Taking a semiconductor factory in a science park as the research object, Case 1 is a parallel chiller system composed of three chillers with a cooling capacity of 800RT. The specific performance parameters of the three chillers are shown in Table 1. Assuming that the total demand on the user side is 40%, 50%, 60%, 70%, 80%, and 90% of the total cooling capacity, the analysis of the present invention constructs the following figure 1 The central air-conditioning distributed control system is shown, and ADMM-GBS optimization calculation is used to obtain a more optimal solution.
[0124] Table 1 Performance parameters of each equipment in the parallel chiller system
[0125]
[0126] In this embodiment, firstly, a mathematical model of chiller power is established according to the correspondence between the performance parameter COP of each chiller and the load rate PLR of each host:
[0127] P chiller =a+b×PLR+c×PLR 2 +d×PLR 3
[0128] In the formula, a , b, ...
Embodiment 2
[0162] Taking a semiconductor factory in a science park as the research object, the parallel chiller system in Case 2 consists of four chillers with a cooling capacity of 1280RT and two chillers with a cooling capacity of 1250RT. In the case, due to long-term operation of each chiller, its design temperature, There are differences in the flow rates, resulting in different characteristic curves of the chillers. The specific performance parameters of the six chillers are shown in Table 3. Assuming that the total demand on the user side is 40%, 50%, 60%, 70%, 80%, and 90% of the total cooling capacity, the analysis of the present invention is constructed as figure 1 The central air-conditioning distributed control system is shown, and ADMM-GBS optimization calculation is used to obtain a more optimal solution.
[0163] Table 3 Performance parameters of each equipment in the six parallel chiller system
[0164]
[0165] In this embodiment, a mathematical model of chiller power...
PUM
Login to View More Abstract
Description
Claims
Application Information
Login to View More 


