Head-machine first water pump behavior full-group start test method for pump storage plant
A technology of pumped storage power station and test method, applied in the field of start-up test of the whole group of pumped storage power station, can solve the problem of large power consumption for water charging and the like
- Summary
- Abstract
- Description
- Claims
- Application Information
AI Technical Summary
Problems solved by technology
Method used
Examples
Embodiment
[0035] Embodiment: The whole group start-up test method of the first water pump working condition of the first machine of the pumped storage power station includes the following steps in sequence:
[0036] 1. The conditions that must be met before the entire unit starts the test:
[0037] (1) The upper reservoir has been completed and has passed the safety appraisal, and has the conditions for water storage operation; the lower reservoir has passed the inspection and acceptance and has been stored, there are no large floating objects in front of and behind the trash rack at the water inlet, and the water storage level and water storage capacity of the lower reservoir All meet the requirements of the unit start-up test; the hydraulic monitoring systems of the upper and lower reservoirs function normally, and the remote transmission of signals is correct.
[0038] (2) The filling and draining tests of the 1# tail water delivery system and the 1# diversion water delivery system h...