The invention discloses an operating method of a charging
pile monitoring room air-conditioning
system. The operating method comprises a
temperature control operating process and a
humidity control operating process. The
temperature control operating process comprises the steps that when the initial temperature in a monitoring room is higher than 25 DEG C, the charging
pile monitoring room air-conditioning
system operates according to a first operating mode; when the temperature in the monitoring room is less than or equal to 25 DEG C and is greater than or equal to 18 DEG C, a compressor stops operating; and when the temperature in the monitoring room is less than 18 DEG C, the charging
pile monitoring room air-conditioning
system operates according to a second operating mode. The
humidity control operating method comprises the following steps that when the
relative humidity is lower than 45%, the charging pile monitoring room air-conditioning system operates according to the first operating mode; when the
relative humidity is greater than or equal to 45% and is less than 70%, neither humidification nor dehumidification operation is carried out; and when the
relative humidity is higher than 75%, the charging pile monitoring room air-conditioning system operates according to the second operating mode. The temperature and
humidity in the monitoring room can be kept in constant intervals all year around, the requirements of the monitoring room of a charging pile are met, the flow of a
refrigerant is adjusted by employing the temperature variation in the monitoring room so that the charging pile monitoring room air-conditioning system is kept in stable operating state for a long time, and frequent starting and stopping of various components are not required.