The invention relates to a 
processing method for distribution network 
short circuit fault, in particular to a method for detecting the distribution network 
short circuit fault and restoring power supply in a non-broken-down section, and capable of achieving 
feeder line automatic local control. 
Short circuit fault detectors A (29) to M (41) are utilized for detecting the 
short circuit fault, and then reclosing time selection devices A (16), B (17), C (18) and D (19) are utilized for restoring power supply in the non-broken-down section. When short circuit happens, outlet switch A (1) or B (2) and C (2) protect the 
tripping in a 
relay way, and during permanent short circuit, the outlet switch A (1) or B (2) and C (3) protect the 
tripping of a second time in the 
relay way, a 
short circuit fault switch is pressed to achieve zero current 
tripping closedown, and a non-fault switch detects 
residual voltage cut-off and closedown for the second time. The outlet switch A (1) or B (2) and C (3) are coincided for the second time, so that the fault section is separated, the 
operation time limit of the non-fault switch is longer than the second reclosing time, three-phase normal 
voltage can be obtained, and the tripping no longer happens. As for the condition that the power is supplied by round network, one side of an 
interconnection switch (23) is deprived of 
electricity, non-fault switch for switching-on and tripping is delayed, and the 
voltage switching-on is detected in sequence.